Gate Will Not Operate with Monitored Entrapment Devices Installed
Contact Edge with 10K Resistor Monitoring
- Verify that dip switch DS2 switch 4 (contact edge monitor) is ON, pressed down on the right-hand side.
- Press and hold the LED indicator button on the control board.
- Verify that the D5 LED (contact edge 2nd entrapment) located in the bottom left corner of the control board is ON dimly.
- If it is not, use a DC voltmeter to measure the voltage on J2 pin 6 to ground. The reading should be approximately 2.5 VDC.
- Activate the contact edge by depressing it and verify that the D5 LED turns ON bright or that the voltage drops to 0 VDC.
- If the reading is 5 VDC, check the wire connections from the contact edge for proper connection.
- If the wire connections are correct, disconnect the contact edge wires from the J2 connector.
- Using an ohm meter, verify the resistance measured between the two contact edge wires. It should be 10K.
- If the resistance is not 10K, the contact edge is bad.
Photo Eye N/C Contact Monitoring
- Verify that DS1 dip switch 10 is ON, pressed down on the right-hand side.
- Verify that dip switch DS1 switch 8 (photo eye monitor) is ON, pressed down on the right-hand side.
- Turn dip switches DS1 3 and 4 OFF to allow power to be applied to the photo eye.
- Press and hold the LED indicator button on the control board.
- Verify that the D11 LED (photo eye N/C 2nd entrapment) located in the bottom left corner of the control board is ON.
- If it is not, verify alignment between the photo eye transmitter and receiver. Correct if necessary.
- If alignment is good, check the wire connection from the photo eye for proper connection.
- If D11 is ON, verify that the D11 LED turns OFF when the photo eye beam is broken.
- If D11 does not turn OFF when the beam is broken, the photo eye is bad.
Patriot RSL Troubleshooting Guide